ACCESS BOARD RESEARCH

Interfacing Accessible Pedestrian Signals (APS) with Traffic Signal Control Equipment           PDF version

April 2003Pedestrian with guide dog at intersection with audible pedestrian signal.

David A. Noyce, Ph.D., P.E.
University of Wisconsin — Madison
University of Massachusetts — Amherst

Janet M. Barlow, C.O.M.S.
Certified Orientation and Mobility Specialist
Atlanta, GA

TABLE OF CONTENTS

ABSTRACT
INTRODUCTION
RESEARCH OBJECTIVES
TRAFFIC SIGNAL CONTROLLERS
ACCESSIBLE PEDESTRIAN SIGNAL (APS) TECHNOLOGIES
INTERFACING APS DEVICES WITH TRAFFIC SIGNAL CONTROL EQUIPMENT
LESSONS LEARNED FROM EXISTING INSTALLATIONS
APS PRODUCTS AND MANUFACTURER INFORMATION
APS MANUFACTURER CONTACT INFORMATION
APPENDIX A - TRAFFIC SIGNAL CONTROLLERS
APPENDIX B - REFERENCES

The products shown in this report are only intended to serve as illustrated examples and are not intended as endorsements of the products. Other products may be available. The Access Board does not evaluate or certify products for compliance with its accessibility guidelines. Users are advised to obtain and review product specifications for compliance with the accessibility guidelines.


ABSTRACT

The primary objective of this research was to provide detailed accessible pedestrian signal (APS) product information specifically focused on the interfacing of APS devices and traffic signal controllers. Information on the various traffic signal controllers used today is also provided. The information is intended for traffic engineers, traffic signal technicians, and others who are implementing APS technologies.

This report addresses the following information:

Contact information for APS and traffic signal controller manufacturers is provided. Funding for this research was provided by the U.S. Access Board. The authors would like to thank Joseph Herr, VHB; Billie Louise Bentzen, Accessible Design for the Blind; Paul Vetter, Edwards and Kelcey; and David Grilley, City of Portland, OR for providing information used in this report and for their thorough, thoughtful, and timely review of the draft manuscript. Their comments and suggestions led to many important improvements in content and description.


INTRODUCTION

The Millennium Edition of the Manual on Uniform Traffic Control Devices was the first to incorporate standards for accessible pedestrian signals (APS) (1). APS is defined as a device that communicates information about pedestrian timing in a non-visual format such as audible tones, verbal messages, and/or vibrating surfaces. Chapter 4E of the MUTCD, “Pedestrian Control Features” includes criteria for the implementation of APS devices into existing traffic signal systems. Information is provided on audible tones and verbal messages, vibrotactile features, pedestrian detectors, and pushbutton locations. A task group of the Signals Technical Committee and National Committee on Uniform Traffic Control Devices (NCUTCD) led the development of the new provisions.

Several companies,located in the United States, Europe, and Australia, manufacture APS products that provide information in non-visual formats. Newer technologies provide speech, location, and mapping features at the push button; these devices have different installation requirements than the cuckoo/chirp pedhead-mounted speakers familiar to many United States traffic engineers. New APS devices are ambient sound responsive and may have tactile arrows, mapping, and speech information and location features that require different sound adjustment, wiring, and installation considerations.

APS devices that make information about the status of signal phases available to visually impaired pedestrians can provide significant benefits in usability, safety, and independence (2, 3). Nevertheless, the recent influx of new APS products has led to some confusion concerning installation criteria and compatibility with current U.S. traffic signal controller equipment. Additionally, several transportation agencies that have recently installed one or more of the APS devices have reported minor problems in their installation and operation; most have proved to be easily correctable.

Concerns with the installation of APS devices have included:

Although the APS devices in each case were installed with the best of intentions, installation deficiencies can create a real safety concern for the blind pedestrian and frustration for the traffic engineers and professionals responsible for the traffic signal system. Traffic professionals, and those who install APS devices, need to be knowledgeable on the product features and installation requirements to assure that all appropriate features are included and operate correctly.


ESEARCH OBJECTIVES

The primary objective of this research was to provide specifiers and installers with the information needed for problem-free operation of APS devices. To fulfill this objective, detailed APS and traffic signal controller product information is provided, specifically focused on the interfacing of APS devices and traffic signal controllers. Information includes:

- Wiring requirements; - Power requirements; - Interaction with conflict monitoring technology;

The following sections provide a description of each of the above items.


TRAFFIC SIGNAL CONTROLLERS

Control of vehicle and pedestrian movements in the U.S. via traffic signals has been in place for over 100 years. The earliest traffic signals were manually operated, requiring a police officer or city employee to manually “switch” traffic flow by changing red and green panels or lights in a switch stand. As traffic continued to grow, it became obvious that mechanical/electrical signal controllers were required to relieve police officers of their traffic control duties.

Electrically operated traffic signals have been in operation in the U.S. since 1914. Electric traffic lights were first installed in Cleveland, Ohio, at Euclid Ave. and 105th Street (4). The traffic signal consisted of two long cross-arms, red and green lights, and buzzers. Two long buzzes signaled Euclid Avenue traffic to proceed, one long buzz meant it was 105th Street's turn to go. Note that this signal had both a visual and audio component.

Since then, traffic signal control equipment has undergone continual improvement. The earliest signal controllers used motors and gears to time the durations of the signal indications; some of these controllers can still be found in use. Technology and the computer era have brought microprocessor-based signal control equipment to what we have today, a complex yet functional system of automated control located at more than 300,000 intersections.

Current Controller Standards

Two standards are used today for traffic signal controllers (5, 6). The National Electrical Manufacturers Association (NEMA) developed one controller standard. Two generations of the NEMA standard are used today, namely the TS 1 (1976) and the TS 2 (1992). The TS 2 is further divided into Type 1 and Type 2 controllers. A second standard was developed by the California Department of Transportation (Caltrans) and the New York Department of Transportation (NYDOT). The original standard was developed under the Type 170 platform in 1979. Updated platforms have included the Type 179, Type 170E, and Type 2070.

Detailed information about these standards and controller features is provided in Appendix A of this document.


ACCESSIBLE PEDESTRIAN SIGNAL (APS) TECHNOLOGIES

Accessible pedestrian signals (APS) are enhancements to the traffic signal system to provide signal phase information in audio, tactile, and/or vibrotactile formats for the pedestrian. APS devices available today are of four general types: pedhead mounted, pushbutton integrated, vibrotactile only, and receiver-base

Pedhead-mounted APS are the only type that have been commonly installed in the U.S. for the past 25 years. This type has a speaker on top of or inside the pedhead with a bell, buzzer, cheep, cuckoo, speech message, or some other tone during the walk phase of the signal only. Some models respond to ambient sound, becoming louder when the traffic noises are louder and quieter when the traffic is quiet. They are usually intended to be heard across the street and act as a beacon, and are relatively loud as a consequence. Manufacturers include Mallory, Novax, US Traffic, and Wilcox. Prisma and Campbell also have an optional additional pedhead mounted speaker that can be used in conjunction with their pushbutton integrated device

Pushbutton-integrated APS have a speaker and a vibrating surface or arrow at the pedestrian button. The sound comes from the pedestrian pushbutton housing, rather than the pedhead. This type has been common in Europe and Australia for years and can be used at both actuated and fixed-time signal timing locations. A constant quiet locator tone, repeating once per second, provides information to the blind individual about the presence of a pedestrian pushbutton and its location. The locator tone is intended to be audible only 2 to 4 meters (6 to 12 feet) from the pole or from the building line, whichever is less.

The walk interval may be indicated by the same tone at a faster repetition rate (Panich, Prisma), by a speech message (Polara, Campbell, Novax, Prisma), or by other tones (Campbell, Polara, Novax). All devices of this type respond to ambient sound levels. These signals are intended to be loud enough to be heard only at the beginning of the crosswalk, although volume can be increased by special activation (Polara, Prisma, Campbell). Manufacturers include Campbell, Georgetown Electric (locator tone not ambient sound responsive), Novax (locator tone and vibrotactile arrow combined with pedhead speaker), Panich, Polara, and Prisma.

Vibrotactile-only APS provide only vibration at the pedestrian pushbutton. The arrow or button vibrates when the WALK signal is on. It must be installed very precisely next to the crosswalk to be of value, and the pedestrian must know where to look for it. Manufacturers include Campbell and Georgetown Electric.

Receiver-based APS provide a message transmitted by infrared or LED technology from the pedhead to a personal receiver. The pedestrian scans the intersection with the receiver to receive the message emitted on the pedhead. These devices may also give other types of information, including information about the name of the streets or the shape of the intersection. Manufacturers include Relume and Talking Signs.

The section on APS devices provides details of each of the APS devices available at the time of this report. Information was obtained from phone, e-mail, Internet, and mail contacts with manufacturers and from the draft report, Accessible Pedestrian Signals: Synthesis and Guide to Best Practice by Accessible Design for the Blind [www.accessforblind.org], being prepared as part of NCHRP Project 3-62: Guidelines for Accessible Pedestrians Signals (7). A matrix summarizing features provided by each device is also included.

Information about APS devices produced by the following manufacturers is included in this publication:

For more information on intersection design to accommodate APS, consult the references and associated web sites.


INTERFACING APS DEVICES WITH TRAFFIC SIGNAL CONTROL EQUIPMENT

APS devices work with existing traffic signal controller logic to provide the desired information to the pedestrian. Most APS devices require no additions or activity within the traffic signal controller cabinet for installation and operation. APS devices are designed to work with either the green, red, WALK, or DON’T WALK indications, and to coordinate calls with the pedestrian pushbutton. Therefore, existing wiring from the traffic signal controller to the pedestrian signal heads and pushbuttons is maintained and unaltered. There is nothing done to the traffic signal controller during the installation of an APS device. In most cases, the only way a traffic controller system knows that an APS device is present is if voltage problems in the APS unit are detected by the controller’s conflict monitor.

In most cases, the APS device is driven by the pedestrian signal head (pedhead) indications. When electrical power is sent to the pedhead to illuminate the WALK indication, the APS device is also activated. All units currently available are wired in some way to the pedestrian signal wiring.

APS devices that are pedhead-mounted provide sound only during the walk interval. These devices are typically wired directly to the WALK indication, without other features or issues.

APS devices that are pushbutton integrated have additional control units that may be installed (depending on the manufacturer and the device) in the pedestrian signal head (16" clamshell style, typical) or contained completely within the pushbutton unit. At least one manufacturer also provides control units that can be installed in the traffic controller cabinet in lieu of the pedhead. Some provide a separate housing that must be mounted on the signal pole. Control units control operation of the locator tone, pushbutton messages and other features available on the pushbutton integrated devices. Pushbutton-integrated devices can also function at pretimed intersections, without pushbutton operation.

Receiver-based devices vary depending on the type of signal. Some include a control unit mounted in the pedhead will others include a replacement pedhead that is installed and wired as a regular pedhead.

Wiring and Power Requirements

The control units for integrated APS devices require additional wiring, most often from the pedhead to the pushbutton. Wiring requirements are quite similar with each mounting strategy. Power requirements are consistent with the traffic signal controller, pedhead, and pushbutton specifications directed by NEMA. APS control units in the pedhead usually convert the 120 VAC to a lower voltage (24 VDC) to the pushbutton. Specific wiring and power requirements are described with each APS device later in this report.

Interaction with MMUs and Conflict Monitors

The MMU, or conflict monitor, performs several functions, the most important of which is to prevent two conflicting green indications from being illuminated. The conflict monitor is really a voltage monitor, looking for inappropriate voltages in inappropriate locations or voltages that are above or below desired levels. The conflict monitor will track multiple components, including the cabinet field wiring terminals for voltage on conflicting signal indications and cabinet voltage to assure that the proper operating range is maintained.

APS devices do not directly interact with the conflict monitor, outside of the fact that the voltage requirements and outputs from the APS units will be monitored within the system specifications. Problems with APS devices can develop when the voltage outputs exceed current conflict monitor limits. When this happens, the conflict monitor overrides the signal control system and places the signal into flash mode. Other problems exist when additional wiring is added from the pedhead to the pushbutton that creates a separate circuit that is no longer detectable by the conflict monitor. Some discussion of this problem is included in the troubleshooting described in the next section, “Lessons Learned from Existing Installations.”


LESSONS LEARNED FROM EXISTING INSTALLATIONS

Interfacing new APS devices with modern traffic signal control systems is not as problematic as industry initially believed. Most APS devices do not interface with traffic signal controllers at all, and those that do only provide equipment inside the cabinet. Problems experienced to date have been minor and correctable; issues presented are not dissimilar to any device associated with traffic signal systems. Many of the problems seem related to a lack of understanding by installers, who may not yet be familiar with the new types of devices, wiring, and the use of the various features. Pushbutton-integrated devices require additional wiring between the pedhead and pushbutton, more attention to pushbutton placement and alignment, and careful adjustment of sound volumes. APS devices provide a real benefit to all pedestrian movements at a signalized intersection. The information presented in this section can help those who use and/or install APS devices to avoid problems.

As with any new technology, the first installation of a new type of APS device may not always operate flawlessly. However, most are easily solvable, either by manufacturers’ adjustments to their devices or by adjustments to the installation. Key issues discussed here include:

APS/Conflict Monitor Compatibility

APS compatibility with the MMU/conflict monitor is related to voltage issues. When unexpected voltages or voltages outside of a given range are detected, the MMU overrides the controller functions and places the signals into a flash mode until maintenance is performed. Most problems in this area have been identified by installers; manufacturers have made modifications to prevent such problems in the future.

Some of the APS devices manufactured internationally were designed with different voltage standards — voltage ranges that differ from current U.S. specifications. In reducing the voltage requirements to the pushbutton, another issue developed with one manufacturer. Some equipment was designed to send 120 VAC to the pushbutton to provide the vibrating surface during WALK, when 24 VDC or less is desired in the US. A circuit to reduce the voltage was successfully created, but the resultant circuit was external to the pedestrian wiring and therefore undetectable by the conflict monitor. In this installation, the conflict monitor would not override the conflicting pedestrian signals nor would the signals be placed into a flash mode when a pedhead malfunction occurred. The manufacturer has developed an alternative vibrating pushbutton that operates with appropriate voltage at the pushbutton and does not require an extra circuit.

Wiring Some problems have also been experienced with wiring and color code practices of devices manufactured abroad. Some device manufacturers used European or Australian wire color practices and standards. These practices are not consistent with what is commonly used in the U.S., resulting in some wiring confusion. Although NEMA and the U.S. National Electrical Code (NEC) do not specifically define system wire color codes, many locations have developed color requirements and "rules-of-thumb." Some color codes that existed in years past have been eliminated for safety reasons assuring that technicians working with the signal wires don’t assume a wire function based on color alone. Therefore, all wires should be tested to identify its use, regardless of color. International companies have developed devices for U.S. installation but care should be taken to review the instructions and wiring of the devices to assure that devices are wired properly. Installers should not assume the function of a wire by its color.

Some of the APS devices manufactured internationally were designed with different voltage standards — voltage ranges that differ from current U.S. specifications. Particularly, foreign devices drew concern from signal technicians over the high voltage sent to the pushbutton location. Voltage to the pushbutton was originally 120 VAC, compared to 24 VDC typical in the U.S. Technicians were concerned about pedestrian safety if the push button is damaged or the push button is taken off by a passing vehicle, and a pedestrian comes in contact with the live wires or electrically charged metal pole. US models with transducers mounted in the pedestrian signal head have been developed. The problem was resolved by placing transducers in the system to reduce the voltage from the pedhead to the pushbutton location. Units with voltages common to U.S. installation are now being produced by all manufacturers listed in this report.

Some problems were initially found with the controller recognizing the pedestrian pushbutton actuation. Most pushbutton units have been found to work well with both the NEMA and 170 controllers because both (along with the conflict monitors) are sensitive to electrical deficiencies. APS devices may be more sensitive to electrical differences than a typical pushbutton. A minor electrical short, not affecting a standard pedestrian push button, prevented an APS installation from working properly. The electrical short was identified and removed using common diagnostic procedures.

Pushbutton Installation

Pushbuttons are often installed on the most adjacent pole to the intersection. At times, two pushbuttons with vibrotactile outputs may be installed on the same metal pole. Vibrotactile APS devices require insulation and a rubber gasket to eliminate vibrations generated from the other pushbutton. Without vibratory insulation, pedestrians may not be able to determine which device has the WALK indication since both will vibrate. Proper insulation of all pushbutton installations (or separate poles) will prevent this problem from occurring.

Phasing

A potential issue with wiring of APS devices is the conflict monitor interface, making sure the device communicates with the traffic signal system. When traffic signals go into flash mode, the APS device must not remain in WALK mode. This problem can be avoided by correctly wiring the APS device into the controller/signal system so the controller logic and conflict monitor can detect and change the pedheads to the appropriate indications.

When a phase rests in WALK, either the WALK indication continues for several minutes at a time or a pushbutton is needed to start the tone, speech, and/or vibratory indications. If continuous, the WALK sound can be irritating for neighbors, even at a quiet volume, so it may be preferable to have it begin in response to actuation in residential settings. With semi-actuated phasing, a pushbutton is usually not provided when crossing alongside main street traffic since the main street approach does not have vehicular actuation. However, when the APS device is provided and the traffic signal is coordinated or on a fixed cycle, the accessible indication will not initiate until the next cycle when the pushbutton is pushed. Therefore, actuating the pushbutton will provide no information until the next signal cycle is started. Pedestrians may assume the pushbutton is not working and attempt to cross without the aid of the APS device. When the pushbutton is pushed, appropriate messaging is recommended as a speech pushbutton information message to indicate that the signal provides a walk interval on the next cycle. When this type of signal phasing is used, appropriate communication between the APS device and the signal system should be evaluated.

Another scenario caused problems with pedestrian signals that rest in WALK or DON’T WALK. A signalized intersection included a pedestrian signal to cross the side/minor street that rested in DON'T WALK unless the pedestrian pushbutton was pushed to cross that street. This signal had coordination and a fixed cycle. When the pushbutton was pushed, two results could occur: 1) if the button was pushed during the side street phase, the WALK was displayed at the start of the corresponding main street phase for a minimum time followed by the Flashing DON'T WALK and the steady DON'T WALK; 2) if the button was pushed during the corresponding main street phase, the WALK was displayed only if there was enough time for the WALK and Flashing DON'T WALK time prior to the force-off period allowed by the coordination. This installation required a time period or “window” at the beginning of the main street phase which was the only period that would allow the WALK to come up while in that phase; otherwise, the WALK would not come up until a side street phase started and terminated, i.e., the next signal cycle. Therefore, a pedestrian could activate the pushbutton and not receive a timely walk interval. Again, a pedestrian may assume that the push button is not working under this condition.

Speakers/Volume

A Maryland installation experienced problems adjusting the volume of a unit that used the APS control units installed in the controller cabinet (rather than the pedestrian signal head). Because of the distance, the wiring was too small of a gauge to drive the speaker and provide a loud enough message, compounded by the pole and speaker being more than 10 feet back from the crosswalk. Manufacturer’s guidelines and specifications should be followed for proper operation. However, there were also concerns and constraints on the amount of room for new wiring in the conduit. Speakers can be provided for each control unit.

Pedhead mounted speakers in existing installations are often mounted in positions that make the messages ambiguous. The speaker should be as close as possible to the crosswalk being signaled by the speaker and speakers should be separated by 10 feet, if possible. For pushbutton integrated devices, the speaker is in the pushbutton housing. The location of the pushbutton and orientation of the speaker can be critical to hearing the WALK indication at the beginning of the crosswalk.

Although current standards call for the APS volume to be 2 to 5 dB above ambient sound and for the locator tone to be heard from 6 to 12 feet from the pushbutton, volume is often set much louder than that. Installers are used to devices using audible beaconing and think that APS are supposed to loud enough to hear across the street. While the locator tone and WALK indication volume can be measured on the street, it is difficult to get an accurate reading, because of the short duration of the tones or messages and their response to ambient noise. Installers need to understand the distance requirements for audibility of the locator tone and make adjustments to the device.

Speech Messages

The speech messages used for the WALK indication, as well as the descriptive pushbutton message, must be understandable. Some problems have been reported. An example of this was found at an intersection where the poorly recorded WALK messages made the street names indistinguishable ["Pratt" and "Calvert"]. The recordings were made in-house and the quality of speech and accent were poor. Digital speech messages can be downloaded from an AT&T web site and use of those may be appropriate. Consistent wording and properly recorded messages are necessary for intelligibility in noisy street conditions.

Speech messages have been suggested as one method to solve problems with ambiguity when two pushbuttons were mounted on the same pole. The speech WALK message that provided the street name was supposed to clarify that the WALK message applied to the street that the pedestrian wanted to cross. However, if the speech message does not clarify which street the button applies to, the speech WALK message using the street name does not clarify which street has the WALK indication to a pedestrian who is unfamiliar with the intersection. For example, at the intersection of Harford and Taylor Streets in Baltimore, the pushbutton message just said "Harford and Taylor" (both street names) for all devices. The speech WALK messages said "Walk sign is on to cross Taylor" or "Walk sign is on to cross Harford." This didn’t resolve the ambiguity problem for users who were unfamiliar with the intersection and not sure which street they were crossing, or who did not know which street the pushbutton applied to.

Polk County, Florida wanted to use a male voice for one crossing direction and a female voice for the other. The theory was that this difference would distinguish crossing directions and add to the safety of the crossing. Most devices provide self-recorded messages capability; however, care should be taken in recording messages, in terms of quality, and wording, and particularly ambiguity. Separate poles may be the best solution.

Other minor problems relate to the recommended messages not being used; there is no standard WALK message or standard pushbutton message. Older installations require updated messages consistent with current MUTCD standards. Recommendations for specific wording for speech messages were developed in January 2002 in a report on speech messages prepared by Accessible Design for the Blind (6). Most problems can be resolved by use of wording consistent with messages developed in that report, available online at www.accessforblind.org.

Pushbutton and Tactile Arrow Location

The blind pedestrian must push the button, then line up to cross the street. Some problems have been observed in locations of pushbuttons and poles supporting APS devices. Pushbuttons installed without locator tones may make it impossible to determine that there is a button that must be activated to call the WALK. Many problems exist with pole locations. Poles that are more than 10 feet from the curb line provide real problems activating the pushbutton and then realigning to cross the street. Pushbuttons are often placed in positions that are not reachable from the sidewalk area, are in the bushes, or behind a fence. Stub poles may be needed from some locations. Separating devices on separate poles provides greater effectiveness.

If the original installation specification was not correct, it may limit the arrow direction and location possibilities. The tactile arrow is supposed to point in the direction of travel on the crosswalk and the face of the device is supposed to be parallel to the crosswalk it controls. Some installations have the pole in a poor location, back from the street with the arrow pointing at the street and aligned with the crosswalk direction, but not within the crosswalk area. In other locations, the arrow has pointed a diagonal to the path that should be taken to cross the street. If installers do not understand the arrow’s alignment, they may install it in the wrong direction, particularly if they use the holes from the previous pushbutton.

Braille Signage Installation

Braille indications on the pedestrian signals have been found mounted backwards or with the Braille label for the wrong street. Manufacturers ship them with a label to clarify positioning; however, technicians may make adjustments to the sign and reverse or mix up the Braille plaques.


APS PRODUCTS AND MANUFACTURER INFORMATION

Figure 3 presents a product matrix that lists various types of APS products and their associated Walk indication and other features, as of March 2003. [text version

Matrix of Accessible
Pedestrian Signal Functions
TYPE                      
Pedhead mounted O   X X     O     X X
Pushbutton integrated X O   O X X X        
Vibrotactile   X                  
Receiver based               X X    
WALK INDICATIONS                      
Tones X O X X X X X     X X
Speech messages X     O O X X X X    
Vibrating surface X X   O X X O 0      
Message to receiver               X X    
Audible beaconing O     X   X O        
OTHER FEATURES                      
Pushbutton locator tone X X   O X X X        
Tactile arrow X X   0 X X X        
Pushbutton information message 0     0   0 0        
Automatic volume adjustment X     X X X X     X  
Alert tone 0       X            
Actualtion indicator X     O O X X        
Tactile Map             X        
Braille & raised print information O         O          
Extended button press O     O O X          
Passive sensor circuit X                    
Clearance interval tones O     O   O          

Notes: X = Standard feature; O = Optional feature.


Campbell Company

Type of APS

Pushbutton-integrated iQ APS
Pedhead mounted speaker available

Campbell iQ57 APS device with speakers in front and on sides of pushbutton device. Campbell H frame APS showing raised arrow, a feature of both styles.  Speaker is located under pushbutton.
Figure 1(left): Campbell iQ57 APS device with speakers in front and on sides of pushbutton device. Figure 2 (right): Campbell H frame APS showing raised arrow, a feature of both styles. Speaker is located under pushbutton.

                       

Standard features

Walk indication

Other

Optional features

Walk indication

Other

Installation notes

A driver unit that provides the logic mounts in the pedestrian signal head and is wired to Walk /Don’t Walk signal. Eight conductor 24 awg 7/30 stranded wire is run from the pedhead to the pushbutton location. The control unit , see figure 3, (called a driver module) is designed to fit and be placed in a clam shell-type pedhead. Campbell control unit installed in a 16 inch pedhead.
Figure 3: Campbell control unit installed in a 16 inch pedhead.

An external control unit, to be mounted outside smaller over/under pedheads is available. The WALK and DON’T WALK wiring is connected to the driver module, along with the output connects to the pushbutton and associated speaker units, and microphone accessories. There is no direct wiring application between the controller and the push button unit (it uses 14 awg pair that serves the pushbutton; however, four pair (minimum) or six pair (desirable) of 18-22 awg wires must be run from the push button unit to the corresponding pedestrian head. These wire pairs are connected to the “vibrator”, “speaker”, “pushbutton” and “LED” connections on the control panel. Microphone for automatic volume adjustment is mounted in pedhead. Volume controls must be adjusted by the installer and are located on the controller board.

Pushbutton designed to install on pole with tactile arrow parallel to crosswalk. Care must be taken with placement on the pole to align the arrow correctly.

A wiring diagram for the Campbell device is shown in Figure 4

Driver Module
Wiring Diagram for a Campbell APS Device.

Figure 4: Wiring Diagram for a Campbell APS Device.

Comments

Manufacturer

Campbell Company, Boise,Idaho

http://www.pedsafety.com


Georgetown pushbutton seen from bottom, showing vibrating arrow location.

Georgetown Electric

Type of APS

Vibrotactile-only - VIPB98

Pushbutton-integrated - VIPB99

Figure 5: Georgetown pushbutton seen from bottom, showing vibrating arrow location.

Standard features

Walk indication

Other

Optional features

Installation notes

VIPB99 requires another circuit connection to the WALK/Don’t Walk (locator tone activated by the Don’t Walk and vibrator activated by the Walk) and a 25.2 AC, 450 mA step down transformer to bring the voltage from the 110/120 VAC source down to 24 VAC.

Power is brought from Walk /green lead to the pushbutton.

Transformer is not supplied with the APS.

Comments

No automatic volume adjustment. This device does not respond to ambient sound and does not comply with current MUTCD recommendations or with the Access Board’s Draft Public Rights-of-Way Accessibility Guidelines.

Pushbutton also does not meet the minimum size recommendation, of at least two inches, in the draft Public Rights-of-Way Accessibility Guidelines.

Without a locator tone, pedestrians who are blind or visually impaired may have difficulty locating and using the pushbutton.

Manufacturer

Georgetown Electric, Ltd., Wilmington, DE


Three Mallory devices seen from different angles.

Mallory Sonalert

Type of APS

Pedhead-mounted VSB 110-1 and VSB 110-4

Figure 6: Three Mallory devices seen from different angles.

Standard features

Walk indication

Optional features

Installation notes

The device broadcasts cuckoo/chirp from the pedhead and is usually mounted inside the pedhead. Typically, a single wire is connected to the WALK indication terminal in the pedhead and a second wire is connected to the neutral terminal. When current is sent from the controller to illuminate the visual WALK indication, the APS device is activated for the duration of the walk phase.

Two Mallory devices installed on a pole in Nashville, TN.Davidson County, Tennessee developed a method of installing the device on the pole (Figure 7 at right). A ped-head bracket is used and secured to the pole with band clamps about 7 to 8 feet off the ground. A 6" piece of pipe is screwed into the end of the bracket, and the audible device sits behind the piece of pipe. For wiring, a hole is drilled into the pole, and an electrical connection is made to the walk signal wires. The wires are attached to the audible device,and tape is used to cover the wire connection to the audible device.

Figure 7: Two Mallory devices installed on a pole in Nashville, TN.

Comments

No automatic volume adjustment. This device does not respond to ambient sound and does not comply with current MUTCD recommendations or with the Access Board’s Draft Public Rights-of-Way Accessibility Guidelines.

Without a locator tone, pedestrians who are blind or visually impaired may have difficulty locating and using the pushbutton.

Mallory also sells sound generators in various beeps, siren and chime sounds; these are not recommended sounds for use as AP

Manufacturer

Mallory Sonalert Products, Inc., Indianapolis, IN

http://www.mallory-sonalert.com


Novax Industries

Type of APS

Pedhead-mounted DS 100 APS and DS 2000 APS

Additional components available for DS 2000 with functions of pushbutton and vibrating arrow integrated.

Novax DS 2000 speakers mounted on top of pedheads Novax VibraWalk pushbutton option to provide locator tone and vibrating arrow
Figure 8 (left): Novax DS 2000 speakers mounted on top of pedheads. Figure 9 (right): Novax VibraWalk pushbutton option to provide locator tone and vibrating arrow.

Standard features

Walk indication

DS 100

DS 2000

Other

DS 100 and DS 2000

Optional features

WALK indication

DS 100

DS 2000

Other

DS 2000

Installation notes

Wiring needs will vary depending on setup. Typically, a 3 wire 18 gauge -120 VAC derived from Walk and Don’t Walk indicator is used. Some have concern over the 120 VAC and have modified the system.

Range of response to ambient sound is set by installer.

The speaker box is typically mounted to the signal pole or on top of the pedhead and wired to the WALK and DON’T WALK circuits, along with the common/ground terminal. The device broadcasts the WALK indication from the pedhead speaker. The black wire (provided) is connected to the WALK indication terminal in the pedhead and a white wire (provided) is connected to a neutral terminal in the pedhead. When current is sent from the controller to illuminate the visual WALK indication, the APS device is activated for the duration of the walk phase.

An innovative method of installing the speaker inside the pedhead has been developed by the City of Portland and McCain Traffic

The locator tone and vibrating arrow are an optional additional component of the device. A series of wires run from the pedhead unit to the push button to power the pushbutton speaker, and vibrating arrow. A current problem with Novax is the 120 VAC power that is sent to the pushbutton from the pedhead unit for the vibrating arrow feature. Some traffic engineers are concerned that this is excessive voltage and can be a safety problem if the pushbutton is removed or destroyed. Novax has been working on resolving the issues and developing other options with more typical voltage. This may have been resolved by the time this document is published.

Comments

Internal board and speaker unit available that mounts in the pedhead.

Manufacturer

Novax Industries, Inc., New Westminister, BC, Canada

www.novax.com


Bob Panich Consultancy

Type of APS

Pushbutton-integrated BPC APS

Panich device with large tactile arrow and large pushbutton. Pushbutton mounted on a pole in Australia. Driver unit that is to be mounted on the pole near the pedhead, shown with housing closed and open.
Figure 10 (left): Panich device with large tactile arrow and large pushbutton. Figure 11 (middle): Pushbutton mounted on a pole in Australia. Figure 12 (right): Driver unit that is to be mounted on the pole near the pedhead, shown with housing closed and open.

Standard features

Walk indication

Other

Optional features

Walk indication

Other

Installation notes

The pushbutton assembly is connected to the pushbutton wire pair to the controller. The APS control unit, called driver module in the manufacturer’s information, is mounted in a housing on the pole near the pedhead and wired to the pedhead. A second wire pair is run to the driver module on the pole. The module is wired to the WALK indication and is activated with the voltage to the pedhead. Manufacturers specifications should be consulted for other wiring requirements that are specific to each setup.

Automatic gain control, the level of the tone in response to ambient noise, is set during installation.

Pushbutton designed to install on pole with tactile arrow parallel to crosswalk. Care must be taken with placement on the pole to align the arrow correctly.

Comments

Complies with specifications of the Australian standard; standard pushbutton in Australia.

Manufacturer states that they will provide other features as needed.

Manufacturer

Bob Panich Consultancy Pty. Ltd., Ryde, New South Wales, Australia
http://www.bobpanich.com.au


Polara Engineering

Type of APS

Pushbutton-integrated Navigator APS

Polara Navigator unit installed on a stub pole in Silver Spring, MD. Polara unit photo showing vibrotactile arrow on pushbutton.
  Figure 13: Polara Navigator unit installed on a stub pole in Silver Spring, MD. Figure 14: Polara unit photo showing vibrotactile arrow on pushbutton.

Standard features

Walk indication

Other

Optional features

Walk indication

Other

Installation notes

Four pairs of 18-22 awg wires must run from the control unit to the Navigator pushbutton unit. Pedhead mounted control units or control cabinet control units are available.

One control unit for each device (push button unit). The control unit is installed in a typical 16-inch person/hand clam shell type pedestrian head and is powered from the WALK and DON’T WALK 120 VAC in the pedhead and converts voltage to 24 VDC (max.) to control the push button functions. There is no direct wiring application between the controller and the push button unit (it uses 14 awg pair that serves the pushbutton; however, four pair (minimum) or six pair (desirable) of 18-22 awg wires must be run from the push button unit to the corresponding pedestrian head. These wire pairs are connected to the "vibrator", "speaker", "pushbutton" and "LED" connections on the control panel. A Polara control unit and associated wire connections, is shown in Figure 4. Three 12 to 18 awg wires are also run from the control unit to the pedestrian head power terminals for the WALK, DON’T WALK, and "common" connections. This wire is the 115 VAC connections provided by the signal controller’s load switch. One wire is also required to connect the microphone located on the bottom of the pedestrian head to the control unit.

For new/reconstructed intersections where new wire will be pulled, the control unit can be placed in the controller cabinet. The control unit consists of a shelf mount card rack power supply base station that can hold up to four control units. One control unit is required for each walk phase. A single microphone can be used to control the audible sounds for all control units, or each control unit can have its own microphone. Four pair of 18-22 awg wire are required to each push button unit.

The installer sets separate volume controls for Walk message and locator tone volumes. In addition, microphone sensitivity can be adjusted.

Pushbutton designed to install on pole with tactile arrow parallel to crosswalk. Care must be taken with placement on the pole to align the arrow correctly.

Polara Control Unit Wiring Diagram

Figure 15: Polara Control Unit Wiring Diagram.

Comments

Manufacturer is developing a model that operates with only two wires to the pushbutton and is programmable after installation by a traffic engineer using a handheld PDA type device. The new model will have the capability to alternate signal sounds, to countdown pedestrian clearance interval and present a signal at the far end of the crosswalk only. It is expected to be available by fall 2003.

Manufacturer

Polara Engineering, Fullerton, CA

http://www.polara.com


Prisma Teknik

Type of APS

Pushbutton-integrated: Several models with different standard features, TS-907, TS-903F, TS-904, TS-908

Additional pedhead mounted directional speaker, TS-995, available

Diagram showing different components inside the pushbutton unit. Prisma APS mounted on a pole in Denmark.
Figure 16: Diagram showing different components inside the pushbutton unit. Figure 17: Prisma APS mounted on a pole in Denmark.

Standard features

Walk indication

Other

Optional features

Walk indication

Other

Crosswalk tactile map

Chart showing the selection of standard symbols supplied with the Prisma APS; Photo of Prisma installed on the street with pedestrian using tactile map.

The crosswalk tactile map is a standard features of the Prismatek device. Symbols are standardized in Sweden.

Figure 18 and 19: Chart showing the selection of standard symbols supplied with the Prisma APS.

Figure 20: Photo of Prisma installed on the street with pedestrian using tactile map.

Installation notes

Diagram of prisma volume and sound setting screws, found inside the top of the pushbutton device.Volume min/max levels are adjustable by installer. Diagram at right shows the ettings, inside the top of the device, adjustable with a screwdriver after emoving the cover.

Figure 21: Diagram of prisma volume and sound setting screws, found inside the top of the pushbutton device.

Tactile arrow is mounted horizontally on top of device, allowing some latitude in placement of a pole, while still making it possible to align the arrow parallel with the associated crosswalk.

Control Board of the Prisma unit.Figure 22 at left: Control Board of the Prisma unit.

Push button units are connected directly to the terminal wire connection in a typical mast arm. A seven 18 to 22 awg wire cable is provided with the unit. Wires are connected to the typical push button terminal, red indication terminal, green indication terminal, neutral, and ground. Also, connections are made to power the sound. Voltage to the pushbutton has been 120 VAC which is greater than some of the other devices. A new US model is being released in April 2003 which provides DC power to the pushbutton, with step-down transformers mounted in the pedhead.

Figure 23: A wiring diagram for the Prisma unit as of 2002. A wiring diagram for the Prisma unit as of 2002.
A wiring diagram for the Prisma unit as of 2002 with labels noted below.
  1. Black - DIP switch option activation (see DIP switch)
  2. Brown - 1 second Push button signal out to controller.
    Controller responds 120/230 VAC to light up LED’s
  3. White - 120/230 VAC supply to push button signal.
    Can be connected to Red (4.) if controller allows (neccessary on red only)
  4. Red - 230 VAC Red / DON’T WALK phase
  5. Blue - 0 VAC Neutral
  6. Grey - 230 VAC Green / WALK phase
  7. Green/Yellow - Ground

Comments

New device is being released in April in the US that allows adjustment of the device using PDA device.

Manufacturer

Prisma Teknik, Tibro, Sweden

http://www.prismateknik.com


Relume

Type of APS

Receiver-based

Relumeled pedhead displaying the WALK indication.
Handheld receiver for the Relume device; provides a speech or tactile message to pedestrian when it is pointed at the pedhead.
Figure 24 (left): Handheld receiver for the Relume device; provides a speech or tactile message to pedestrian when it is pointed at the pedhead.
Figure 25 (RIGHT): Relumeled pedhead displaying the WALK indication.

Standard features

Walk indication

Other

Optional features

N/A

Installation notes

Pedestrian signal heads must be Relume LED heads. Speech message recorded in personal receiver is triggered by pulsed light from the Relume LED pedestrian signal display. The pedhead must be carefully positioned to transmit information only within the width of the crosswalk.

Relume devices are simply replacements LED pedheads with typical wiring. However, concerns have been raised about how to provide access to the information to pedestrians who are blind who do not have receivers and do not know where the Relume devices are located.

Comments

Speech message during Walk is not in language specified in MUTCD.

Device has an approximately 15 degree field to pick up signal.

Pedestrians who are blind must have access to receivers.

Pedestrians must know where the Relume pedheads are installed, or they are unlikely to search for or use the available information.

Without a locator tone, pedestrians who are blind or visually impaired may have difficulty locating and using the pushbutton.

Manufacturer

Relume Corporation, Troy, MI

http://www.relume.com


Talking Signs

Type of APS

Receiver-based

Talking signs transmitter mounted on top of pedhead. Closeup of Talking Signs® receiver in left hand.
Figure 26 (left): Talking signs receiver held in a hand; the receiver is approximately 6 inches long with a button on top which the pedestrians push to activate when scanning for messages Figure 27 (right): Talking signs transmitter mounted on top of pedhead.

Standard features

Walk Indication

Other

Optional features

Additional landmark information can be included in the orientation message, as this information is received before users reach the intersection, and it does not interfere wit their ability to hear or attend to traffic and signal information when they are at the crosswalk.

Developments in the technology and installation may include radio transmitted speech or vibratory information to alert travelers to locations where transmitters are installed. This technology, developed under the direction of the Japan National Police Agency, is compatible with the Smith-Kettlewell/Talking Signs® standard.

How Talking Signs works

A bird’s eye view of Talking Signs® infrared transmitter system for intersections.

Figure 28: A bird’s eye view of Talking Signs® infrared transmitter system for intersections.

The above illustration shows how the Talking Signs infrared transmitter delivers messages to the pedestrian who is carrying a receiver.

Wide beam tells:

Narrow beam tells:

Installation notes

The transmitter providing signal information must be carefully positioned to provide information only within the width of the crosswalk. Talking Signs has a control board mounted in the unit on the pedhead. The transmitters are wired by connecting one 110 VAC wire to the WALK, DON’T WALK, and common terminal in the pedhead. The current provided to operate the visual pedhead powers the Talking Signs transmitter. The pedestrian who is blind must have a receiver, point the receiver at the talking signs transmitter, and push the button to hear the message, ‘Walk sign is on’, or ‘Wait’, depending on the status of the walk indication.

Comments

Infinitely variable messages recorded in transmitters.

Receivers usable for many wayfinding tasks where transmitters are installed.

Pedestrians must know where the TS transmitters are installed, or they are unlikely to search for or use the available information.

Pedestrians who are blind must have access to receivers.

Infrared beams can be difficult to detect in some weather conditions.

Manufacturer

Talking Signs Inc., Baton Rouge, LA

http://www.talkingsigns.com


Photo of the US Traffic device mounted on top of a pedestrian signal head.

U.S. Traffic Corporation

Type of APS

Pedhead-mounted APS 10 -

Figure 29: Photo of the US Traffic device mounted on top of a pedestrian signal head.

Standard features

Walk Indication - tones

Other

Optional features

Not available

Installation notes

This devices broadcasts cuckoo/chirp from a speaker mounted on the pedhead and is wired into the pedhead in the appropriate direction. A small hole is drilled into the top of the pedhead or in the signal pole, and the device is connected. A black wire (provided) is connected to the WALK indication terminal in the pedhead and a white wire (provided) is connected to a neutral terminal in the pedhead. When current is sent from the controller to illuminate the WALK indication, the APS device is activated during the duration of the walk phase. This device has a PC board that plugs into the unit and is housed inside the APS unit to adjust the sound using two settings, initial volume with no traffic (volume) and volume level increase with traffic (feedback). Figure 30 shows the APS-10 control board.

Typical PC Board and Control Unit of U.S. Traffic APS Device

Figure 30. Typical PC Board and Control Unit of U.S. Traffic APS Device

Comments

Manufacturer is developing a device that provides audible countdown information.

Without a locator tone, pedestrians who are blind or visually impaired may have difficulty locating and using the pushbutton.

Manufacturer

U.S. Traffic Corporation, Santa Fe Springs, CA

http://www.ustraffic.net


Wilcox SalesPhoto of pedhead with Wilcox APS mounted on top.

Type of APS

Pedhead-mounted - PS/A 10

Figure 31: Photo of pedhead with Wilcox APS mounted on top.

Standard features

Walk indication

Other

Not Available

Optional features

Not Available

Installation notes

Device broadcasts cuckoo/chirp from a speaker mounted on the pedhead and is wired into the pedhead in the appropriate direction. A small hole is drilled into the top of the pedhead or in the signal pole, and the device is connected. A black wire (provided) is connected to the WALK indication terminal in the pedhead and a white wire (provided) is connected to a neutral terminal in the pedhead. When current is sent from the controller to illuminate the WALK indication, the APS device is activated during the duration of the walk phase.

Mixed volume is adjusted by installer.

Comments

No automatic volume adjustment. This device does not respond to ambient sound and does not comply with current MUTCD recommendations or with the Access Board’s Draft Public Rights-of-Way Accessibility Guidelines.

Without a locator tone, pedestrians who are blind or visually impaired may have difficulty locating and using the pushbutton.

Wilcox is also developing an audible sign using same speaker technology.

Manufacturer

Wilcox Sales Company, Claremont, CA
http://www.wilcoxsales.com


APS MANUFACTURER CONTACT INFORMATION

These manufacturers offer Accessible Pedestrian Signal products.

Campbell Company
221 West 37th Street, Suite C
Boise, Idaho 83714
Phone: (877) 345-1727, (208) 345-7459
Fax: (208) 345-7481
Web: www.pedsafety.com

Georgetown Electric, Ltd.
2507 West Second Street
Wilmington, DE 19805
Phone: (302) 652-4835
Fax: (302) 652-6447

Mallory Sonalert Products, Inc.
4411 South High School Road
Indianapolis, IN 46214
Phone: (317) 612-1000
Fax: (317) 612-10
Web: www.mallory-sonalert.com

Novax Industries, Inc
658 Derwent Way
New Westminster, BC
V3M5P8 Canada
Phone: (604) 525-5644
Fax: (604) 525-2739
Web: www.novax.com

Bob Panich Consultancy Pty. Ltd.
48 Church Street
P.O. Box 360
Ryde, NSW 2112, Australia
Phone: 61 2 9809 6499
Fax: 61 2 9809 6962
Web: www.bobpanich.com.au

Polara Engineering
4115 Artesia Avenue
Fullerton , CA 92833-2520
Phone: (888) 340-4872
Phone: (714) 521-0900
Fax: (714) 522-8001
Web: www.polara.com

Prisma Teknik AB
P.O. Box 5, S-543 21
Tibro, Sweden
Phone: (46) 504 150 40
Fax: (46) 504 141 41
Web: www.prismateknik.com

Prisma Teknik US distributor:
Eagle Traffic Control Systems
8004 Cameron Road
Austin, TX 78754
Phone: (512) 837-8310
Fax: (512) 837-0196
E-Mail: info@eagletcs.com
Web: www.eagletcs.com

Relume Corporation
64 Park Street
Troy, MI 48083
Phone: 888-7RELUME, (248) 585-2640
Fax: (248) 585-1909
Web: www.relume.com

Talking Signs Inc.
812 North Blvd.
Baton Rouge, LA 70802
Phone: (888) 825-5746
Fax: (504) 344-2811
Web: www.talkingsigns.com

U.S. Traffic Corporation
9603 John Street
Santa Fe Springs, CA 90670
Phone: (562) 923-9600, (800) 733-7872
Fax: (562) 923-7555
Web: www.ustraffic.net

Wilcox Sales Company
1738 Finecroft Drive
Claremont, CA 91711-2411
Phone: (909) 624-6674
Fax: (909) 624-8207
Web: www.wilcoxsales.com


APPENDIX A — Traffic Signal Controllers

TRAFFIC SIGNAL CONTROL

Evolution of Controller Standards

The evolution of both the NEMA and Caltrans/NYDOT standards are presented in Figure 33 below. The NEMA TS-1 traffic signal controller standard was developed in 1976, with the goal of providing interchangeability among manufacturers. All of the equipment and software necessary to support the controller operation was specified. A controller cabinet designed to house the controller and associated equipment was also specified, including all of the supporting wiring and configuration. The standard defined basic actuated intersection control, but did not specify hardware allowing controller capabilities to expand with technology.

A Timeline Showing The Evolution of Traffic Controller Standards From 1920 to Present.

Figure 33. A Timeline Showing The Evolution of Traffic Controller Standards From 1920 to Present

Advances in technology and the desired functionality of the TS 1 controllers created several issues. The TS 1 standard focused on the three primary equipment connectors on the front on the controllers. Manufacturers independently added a fourth connector for preemption, coordination, additional detector inputs, and system communications that were not interchangeable, preventing enhanced controller functions. In some cases, system communications was not part of the fourth connector and was brought in through yet another connector. Additional limitations were identified with pretimed operations and capabilities beyond basic traffic control.

These limitations led to development of the TS 2 controller standard, developed in 1992. The TS 2 standard defined two types of controllers and cabinet architectures, the TS 2 Type 1 and TS 2 Type 2. The TS 2 Type 1 controller is unique in the sense that is uses an RS-232/SDLC data link connection to the peripheral devices, with a separate power connector (5). The TS 2 Type 2 provides the same connectors as the TS 1 but also includes the data link connector. This allows the TS 2 Type 2 controller to be installed in TS 1 cabinets, reducing the upgrade costs. The TS 2 standard defines advanced traffic signal operations such as coordination and preemption, and developed standards for pretimed operations and the cabinet. Advanced cabinet monitoring and diagnostics were defined.

The Type 170 controller standard differed from NEMA standards in that it was a hardware standard only. Software to run the controller can be supplied by independent vendors and designed to perform specific applications. Additional standards were developed for ancillary equipment in the cabinet, and the cabinet itself. The development of the Type 170 controller was an attempt to create a controller that could be used to meet current and future traffic needs. Rather than require hardware modification, as with NEMA controllers, the Type 170 responds to new or changing traffic conditions through upgrades or changes to the software. Nevertheless, some tasks do require hardware modifications and additions.

The Type 170 specification required that hardware be interchangeable among manufacturers. Since the software was independent, the controller was basically a general purpose field computer that could be used for a variety of applications beyond traffic signal control. With the necessary software, a Type 170 controller could operate in a simple 2-phase operation or control the most complex interchange. In 1986, the NYS DOT developed the Model 179 controller standard, and in the early 1990’s, Caltrans developed the Model 170E controller standard. Both were enhancements to the Model 170 standard to meet current needs, and increased processing power, improved user display capabilities, provided larger memory storage, and enhanced communications capabilities.

Only a few years later, in 1995, the rapid advances in computer technology led Caltrans to develop yet another standard, titled the Model 2070. The goal of the 2070 standard was to provide an advanced controller platform to serve a variety of applications and further define processor, operating system, and software language, while maintaining general compatibility with previous controller (Model 170) standards.  Expanded processing power in the Model 2070 controller allowed for use in a wide variety of applications and provided multiple configurations to fit specific system requirements. The addition of optional VMEBUS modules or serial ports provided additional functionality to include video-imaging, changeable message sign control, and various other communication-based functions. The software and hardware interface was standardized, yet the software remained independent of the controller hardware, allowing for software developed specifically for the desired application.

Several different configuration profiles were developed with the Type 2070 family, including the Type 2070N which is compatible with NEMA interfaces and cabinets. Some issues exist today with the Type 2070 platform, specifically related to the limited number of software vendors and the high cost of the controller hardware.

Current activities are focused on developing a new controller standard, coined the Advanced Traffic Controllers (ATC), which combines the best attributes of NEMA, Type 170, Type 2070 along with emerging ideas and technology. The new ATC platform will provide an open architecture, allowing for software portability. Open architecture will also provide additional applications, with the possibility of running multiple applications on one ATC controller. The ATC standard provides flexibility in hardware development, allowing hardware changes to evolve with technology. Interchangeability between manufacturers is strongly emphasized including connectors, user interface, software, communications, internal networks, and computer and modem modules. The flexibility developed with the ATC standards will allow an ATC controller to work in intersection control (including APS), real-time surveillance, transit systems, communications hubs, field masters, ramp metering, sign control, ITE beacons, video systems, environmental systems, and weigh-in-motion applications.

Typical Controller Cabinet Components

NEMA TS 1 and TS 2

Opening the door of a typical NEMA TS 1 controller cabinet will lead you to the controller itself, along with the conflict monitor, detectors, load switches, other peripheral equipment, and the necessary internal wiring. A circulating fan and filtered vent are included with each cabinet to provide air circulation to minimize heat buildup. A light is provided for working in the cabinet during nighttime hours.

The NEMA TS 2 controller assembly is nearly identical to the TS 1. The two primary differences are the change in controller unit and the conflict monitor is replaced by a malfunction management unit (MMU). The MMU is a more advanced device, not only monitoring all of the conflict voltages, but also communicating with the controller providing an additional element of monitoring. The TS 2 controller also uses a bus interface unit (BIU) for communication between the various control components and detectors. The BIU provides a simplification in cabinet wiring while providing flexibility and power (5). The TS 2 assembly contains a shelf-mounted power supply unit that provides the appropriate power to each of the controller devices. The detectors in the TS 2 cabinet are rack-mounted. A typical TS 2, Type 1 cabinet is shown in Figure 34.

Typical TS 2 Type 1 Controller Cabinet and Components.  The Picture Shows The Location of the Controller Unit, Detectors, Conflict Monitor, Load Switches, Flasher, and BIU.

Figure 34. Typical TS 2 Type 1 Controller Cabinet and Components. The Picture Shows The Location of the Controller Unit, Detectors, Conflict Monitor, Load Switches, Flasher, and BIU.

The controller unit itself simply sits on a shelf in the cabinet. Heavy cables run to each of the four ports on the front of the controller. The "A" connector provides power to the controller as well as inputs and outputs to the cabinet (5). The "B" and "C" connectors provide various inputs and outputs for control. The A, B, and C connectors are standardized by NEMA and are interchangeable amongst all manufacturers. Each connector is different, preventing cables from being inserted in the wrong connection port. The "D" connector provides communication, preemption, and expanded detection capabilities which are used in more advanced systems. Typical controllers have eight available detection inputs. The D connector provides input for eight additions detectors. The D connector is used with TS 1 controllers and is not standardized by NEMA, therefore, may not be interchangeable.

The conflict monitor (TS 1) is also shelf-mounted and wired into the controller system. The conflict monitor performs several very important functions, the most important of which is to prevent two conflicting green indications from being illuminated. The conflict monitor is really a voltage monitor, looking for inappropriate voltages in inappropriate locations or voltages that are above or below desired levels. The conflict monitor (5, 6):

The inductive loop detectors, or loop detector amplifiers, provide a direct connection to the inductive loops placed in the pavement. Vehicles that pass over the loops are identified by the loop detector amplifiers through changes in inductance. The detectors send vehicle detection information to the controller.

The flasher unit provides the flash sequence in the traffic signals. The flash sequence is implemented either during off-peak hours, most often during late night and early morning times. The flashers are also used when the conflict monitor overrides the signal system and puts the signals into a flash mode.

The Bus Interface Unit (BIU) links the Controller to the Cabinet input/output (I/O) elements (5). It can also be used as a detector interface device. The BIU is responsible for controlling load switches, providing dimming, receiving and isolating pedestrian calls, analyzing detector faults, time-stamping detector calls, and providing detector resets. By design, the BIU is free of operator controls. The BIU performs its I/O functions based upon a pre-wired card rack address.

The load switches receive output from the controller that relay to the terminals located near the bottom of the cabinet (5). Load switches receive a 12-volt DC input for the green, yellow, and red indications, and outputs 120 volts AC to the green, yellow and red field terminals.

Controllers satisfying TS 2 standards are categorized by Type 1 and Type 2 features (5). TS 2 Type 1 controllers contain high speed data channels and have increased capabilities, provide additional diagnostic data, and consume less power than the TS 1 controllers. TS 2 Type 2 controllers contain all of the features of the TS 2 Type 1, but also include additional connectors for data exchange with the terminals and facilities, and may contain a “D” connector for compatibility with TS 1 controllers.

Type 170 and Type 2070

The Type 170 and 2070 controller assemblies contain all of the same elements as the NEMA TS 1 (5). The controller itself, conflict monitor, detectors, load switches, peripheral equipment, and appropriate wiring are included. The controller assembly has a different look, using a rack-mounted modular setup. The controller assembly has more of a computer server look than the separate unit look of a typical NEMA setup. Detectors, power supplies, and preemption devices are modularly rack-mounted. The card rack for the input and output devices, called the input/output files, are mounted similarly.


TRAFFIC SIGNAL CONTROLLER MANUFACTURERS

Specific information on several traffic signal controllers is presented in the following sections. Information was obtained through phone, e-mail, and Internet contacts with manufacturers. The NEMA controllers are presented first, followed by the Type 170/2070 controllers. General information on conflict monitors and malfunction management units (MMU) is also presented.

Information about traffic signal controllers produced by the following manufacturers is included in this section:


NEMA ControllersEagle EPAC300 Controller Showing Keypad for Entering Information and Wiring Connections.

Eagle

Type of Controller

EPAC300

Figure 35. Eagle EPAC300 Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

The EPAC300 is a fully actuated controller that can operate in an isolated mode or work in coordination with other intersections. Several different models exist, all with features that exceed the National Electrical Manufacturers Association (NEMA) TS 1 (1989) and TS 2 (1998) Actuated Controller Unit Standards.

The EPAC300 controller can work in a very simple pretimed mode or highly complex actuated control including up to 16 vehicles phases, 16 pedestrian phases, four timing rings, 16 overlap phases and 80 detectors. Adaptive control features allow the controller to make adjustments in maximum green times, protected and permissive left-turn phasing, and coordinated phases. The controller operates in a time-based mode, providing the capability to program 250 events, 99 day, and 10 week alternatives. The controller also works in six different modes of coordination. Diagnostic and reporting programs are resident in the controller to aid in maintenance and troubleshooting, and to obtain performance output.

Optional features

Controller types are available that meet TS 1, TS 2 Type 1, and TS 2 Type 2 standards.

Installation notes

EPAC300 controllers require a compatible controller cabinet, conflict monitor/malfunction management unit, and related hardware. Eagle produces a number of cabinets in various sizes.

Manufacturer

Eagle Traffic Control Systems, Austin, TX

http://www.eagletcs.com


Econolite ASC/2S-2100 Controller Showing Keypad for Entering Information and Wiring Connections.

Econolite

Type of Controller

ASC/2S Series

Figure 36. Econolite ASC/2S-2100 Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

The ASC/2S is a fully actuated controller, developed in 1998. This controller contains features that exceed the NEMA TS 1 and TS 2 Actuated Controller Unit Standards, and is compatible with previous NEMA-based models. Software in the ASC/2S is stored in flash EPROMs (read-only semiconductor memory that is erasable), allowing field software updates without changing PROMs (permanent memory in hardware).

The ASC/2S includes up to 12 vehicle phases, 8 concurrent groups, two timing rings, 16 overlap phases and 64 detectors. The controller can operate in a time-based mode, providing the capability to program multiple events, 16 day, and 10 week alternatives. The controller also works in 64 coordination patterns, each with its own cycle, offset and split. Six priority and four bus preemption sequences are available with an optional transit signal priority control.

Diagnostic and reporting programs are resident in the controller to aid in maintenance and troubleshooting, and to obtain performance output.

Optional features

Controller models are available that meet TS 1,TS 2 Type 1, and TS 2 Type 2 standards.

Installation notes

ASC/2S controllers require a compatible controller cabinet, conflict monitor/malfunction management unit, and related hardware. Econolite produces a number of cabinets in various sizes.

Manufacturer

Econolite Control Products, Inc., Anaheim, CA

http://www.econolite.com


McCain McCain Vector GS Controller Showing Keypad for Entering Information and Wiring Connections.

Type of Controller

Vector GS

Figure 37. McCain Vector GS Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

McCain’s Vector controller uses an open architecture design that provides maximum flexibility through use of PC-compatible third-party hardware and software. The controller supports up to 16 phases and 4 rings, consistent with the other controller types.

Optional features

Controller types are available that meet TS 1, TS 2 Type 1, and TS 2 Type 2 standards.

Installation notes

The Vector GS controller requires a compatible controller cabinet, malfunction management unit, and related hardware. Works with NEMA based cabinets and equipment.

Comments

Provides an open architecture that allows for third-party computer cards to be installed with new/revised programming features.

Manufacturer

McCain Traffic Supply
http://www.mccaintraffic.com


Naztec Naztec Series 900 TS 2 Controller Showing Keypad for Entering Information and Wiring Connections.

Type of Controller

980/981

Figure 38. Naztec Series 900 TS 2 Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

The 980/981 is a fully actuated controller that can operate in an isolated mode or work in coordination with other intersections. The basic difference between the Model 980 (Secondary) and the Model 981 (Master /Secondary) hardware is the additional serial port in the maser unit. The master unit also runs additional software allowing it to serve as a master and a secondary controller in a system configuration. This controller contains features that exceed the NEMA TS 1 (1989) and TS 2 Type 1 and Type 2 (1998) Actuated Controller Unit Standards.

Naztec controllers allow the user to program a maximum of 16 phase sequences by assigning up to 16 phases in 4 separate rings (8 phases per ring). This flexibility combined with NTCIP concurrent phase definitions and 16 overlaps provides a phasing solution for single or multiple intersection control and diamond interchange operation.

Built-in diagnostic allows all input/output sigals, RAM devices, and memory to be tested.

Optional features

Controller types are available that meet TS 1,TS 2 Type 1, and TS 2 Type 2 standards.

Installation notes

980/981 controllers require a compatible controller cabinet, malfunction management unit, and related hardware. Works with NEMA based cabinets and equipment.

Manufacturer

Naztec, Inc., Sugarland, TX 77487
http://www.naztec.com


Peek 3000E Controller Showing Keypad for Entering Information and Wiring Connections.Peek

Type of Controller

3000E

Figure 39. Peek 3000E Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

The 3000E is a fully actuated controller that can operate in an isolated mode r work in coordination with other intersections. Several different models exist with various features. This controller contains features that exceed the NEMA TS 1 (1989) and TS 2 Type 1 and Type 2 (1998) Actuated Controller Unit Standards.

The 3000E controller can work in a very simple pretimed mode or highly complex actuated control including up to 16 vehicles phases, 16 pedestrian phases, four timing rings, 16 overlap phases and 64 detectors. A pedestrian override allows over timing of phases due to peds, without skipping or short timing other phases during coordination. The controller can operate in a time-based mode, providing the capability to program 220 events, 32 day, and 20 week alternatives in a 99 year clock. The controller also provides coordination through 120 coordination patterns, 24 cycles, 5 offsets/cycles, 24 splits, and automatic permissives.

Diagnostic and reporting programs are resident in the controller to aid in maintenance and troubleshooting, and to obtain performance output.

Optional features

Controller types are available that meet TS 1, TS 2 Type 1, and TS 2 Type 2 standards.

Installation notes

3000E controllers require a compatible controller cabinet, malfunction management unit, and related hardware. Works with NEMA based cabinets and equipment.

Manufacturer

Peek Traffic, Inc., Sarasota, FL 34236
http://www.peekglobal.com


US Traffic Type of Controller 820A US Traffic Controller Showing Keypad for Entering Information and Wiring Connections.   US Traffic Controller Showing Keypad for Entering Information and Wiring Connections.
  Figure 40 (left). US Traffic Controller Showing Keypad for Entering Information and Wiring Connections.   Figure 41 (right). US Traffic 820A Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

The 820A Series traffic controllers supports various firmware configurations. Features of the 820A OSAM include hardware interconnect capability, both as a secondary and as a time-of-day/day-of-week master. Time-based coordination features 200 events, 16 day plans, 10 week plans, 30 exception days, 16 holidays, and a true yearly schedule. Forty-eight independent coordination plans and 16 traffic responsive free plans provide flexible control with variable phasing. A free or coordinated plan may use any of eight detector plans. Dynamic extension of maximum green time is based on vehicle demand. Max II is selective by time-of-day for each phase. The status of all inputs may be displayed for cabinet wiring verification. On-line diagnostics continuously check for errors and store the last 64 errors with the date and time.

The 820A OSAM also provides remote operations through an RS-232 port that may be connected to a Hayes compatible modem.

Optional features

Controller types are available that meet TS 1,TS 2 Type 1, and TS 2 Type 2 standards.

Installation notes

The 820A controller requires a compatible controller cabinet, malfunction management unit, and related hardware. Works with NEMA based cabinets and equipment.

Comments

Provides an open architecture that allows for third-party computer cards to be installed.

Manufacturer

U.S. Traffic Corporation
http://www.idc-traffic.com


170/179/2070 ControllersEagle 2070 ATC Controller Showing Keypad for Entering Information and Wiring Connections.

Eagle

Type of Controller

2070

Figure 42. Eagle 2070 ATC Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

The 2070 ATC controller is capable of basic intersection control and full communication within traffic management systems. The open architecture allows the use of market software. Works in modular system. Compatible with Type 170 and Type 170E controllers.

Optional features

Can interface with NEMA controllers by using the available interface module.

Installation notes

Requires a compatible controller cabinet, conflict monitor, and related hardware.

Comments

Provides an open architecture that allows for third-party computer cards to be installed with new/revised programmingfeatures.

Manufacturer

Eagle Traffic Control Systems, Austin, TX
http://www.eagletcs.com


 Econolite 2070 ATC Controller Showing Keypad for Entering Information and Wiring Connections.

Econolite

Type of Controller

ATC2070

Figure 43. Econolite 2070 ATC Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

The ATC2070 controller can be configured to fit all 2070, 170, 170E and NEMA applications. The selection of the appropriate input/output module will allow interface between any cabinet type. Modules exist to provide communication within traffic management systems. The open architecture (OS-9 operating system) allows the use of market software. Compatible with Type 170 and Type 170E controllers.

Optional features

Can interface with NEMA controllers by using the available interface module.

Installation notes

Requires a compatible controller cabinet, conflict monitor, and related hardware.

Comments

Provides an open architecture that allows for third-party computer cards to be installed with new/revised programming features.

Manufacturer

Econolite Control Products, Inc., Anaheim, CA

http://www.econolite.com


McCainMcCain 2070 Controller Showing Keypad for Entering Information and Wiring Connections.

Type of Controller

170/2070

Figure 44. McCain 2070 Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

The 2070 and 2070L are based on an open architecture design. The 2070 controller is constructed as a modular system. Each functional part input/output (I/O), Communications, CPU is designed into a separate and removable module. Modules can be replaced or upgraded on an individual basis without having to pull the entire unit. The modules provide parallel and serial I/O for the cabinet interfaces with 64 inputs and outputs arranged in two connectors. The communications modules provide for RS232,RS485, as well as 1200 and 9600 baud modem communication. The software is written in C or C++ and is coded in a modular format. Modules can be added or removed without affecting the rest of the program. The operating system in current use is OS 9. The OS 9 module interfaces between the “C” code and the hardware.

Optional features

Several modules available for desired interfaces.

Installation notes

The 2070 controller requires a compatible controller cabinet, conflict monitor, and related hardware. Works with 2070 based cabinets and equipment.

Comments

None

Manufacturer

McCain Traffic Supply
http://www.mccaintraffic.com


Naztec 2070 Controller Showing Keypad for Entering Information and Wiring Connections.

Naztec

Type of Controller

2070M

Figure 45. Naztec 2070 Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

The 2070 controller is completely compatible with Type 170 and Type 179 controllers. The selection of NEMA input/output module will allow interface with NEMA cabinets. Modules exist to provide communication within traffic management systems. Operating system software is provided with the unit.

Optional features

Can interface with NEMA controllers by using the available interface module.

Installation notes

Requires a compatible controller cabinet, conflict monitor, and related hardware.

Comments

Provides an open architecture that allows for third-party computer cards to be installed with new/revised programming features.

Manufacturer

Naztec, Inc., Sugarland, TX
http://www.naztec.com


U.S. Traffic

Type of Controller

Type 170/179/2070
US Traffic 170 Controller Showing Keypad for Entering Information and Wiring Connections.   US Traffic 179 Controller Showing Keypad for Entering Information and Wiring Connections.
  Figure 46 (upper left). US Traffic 170 Controller Showing Keypad for Entering Information and Wiring Connections.   Figure 47 (upper right). US Traffic 179 Controller Showing Keypad for Entering Information and Wiring Connections.
  Figure 48 (lower center). US Traffic 2070 Controller Showing Keypad for Entering Information and Wiring Connections.   US Traffic 2070 Controller Showing Keypad for Entering Information and Wiring Connections.

Standard features

These controllers use an open systems architecture and have available NEMA TS 1, TS 2 Type 2 Compatible Digital Interfaces. Also compatible with Type 170 cabinets. The controller supports OS 9 and Other Real-Time Operating Systems. Third-Party Software Available for intersection control, communications, and other applications. Through add-on VMEBUS modules or serial ports, other items can be added such as Changeable Message Signs (CMS), Environmental Monitoring Equipment, Video Detection Systems, Camera Control, and various Emergency Monitoring Systems.

Optional features

Several modules available for desired interface.

Installation notes

The 2070 controller requires a compatible controller cabinet, conflict monitor, and related hardware. Works with 2070 based cabinets and equipment.

Manufacturer

U.S. Traffic Corporationhttp://www.idc-traffic.com


Support Equipment

Naztec - MMU

Type of Control

Malfunction Management Unit (MMU) 516

Figure 49. Naztec Malfunction Management Unit (MMU).

Standard features

The Naztec MMU monitors up to 16 traffic signal indications (channels) for conflict, improper sequencing, incorrect timing, and improper signal voltage levels. The MMU is also capable of operating in older TS1 type cabinets, and is compatible with 12-channel Conflict Monitor Units conforming to the TS 1 standard.

All connectors, indicators and operator controls are located on the front panel of the MMU. Channel and control input signals and relay output connections are made through two connectors.Indicators on the front of the MMU provide status and fault information.

The MMU performs continuous diagnostic tests during all operating modes. All memory elements, the microprocessor, operating voltages, and critical circuitry are checked.

Manufacturer

Naztec, Inc., Sugarland, TX
http://www.naztec.com


 Naztec Conflict Monitor.

Naztec — Conflict Monitor

Type of Control

Conflict Monitor Unit (CMU)

Figure 50. Naztec Conflict Monitor.

Standard features

The conflict (and power) monitor is built in accordance with NEMA TS1 specifications.

In addition to standard NEMA requirements, the conflict monitor can be programmed to monitor for short yellow and green intervals, sequence failures, and red failures. Failures can be either logged or latched. A real-time clock allows time and date stamping of all events. LED indicators are used to display all failures. The RS-232 port may be used to interface with a personal computer, printer, or traffic control system. Port setup including baud rate selection is accomplished via the keyboard. Printed reports include Program Options, Fault History, Power History, Tracing, and Program Card.

Manufacturer

Naztec, Inc., Sugarland, TX
http://www.naztec.com


 Naztec Bus Interface Unit (BIU).

Naztec - BIU

Type of Control

Bus Interface Unit (BIU)

Figure 51. Naztec Bus Interface Unit (BIU).

Standard features

The Bus Interface Unit (BIU) links the TS-2 Controller Unit to the Cabinet I/O. It is responsible for controlling load switches, providing dimming, receiving and isolating pedestrian calls, analyzing detector faults, time-stamping detector calls, and providing detector resets. By design, the BIU is free of operator controls. The BIU performs its I/O functions based upon a pre-wired card rack address.

Manufacturer

Naztec, Inc., Sugarland, TX
http://www.naztec.com


Naztec Loop Detector Amplifier Card.

Naztec - Detectors

Type of Control

Detector

Figure 52. Naztec Loop Detector Amplifier Card.

Standard features

The Inductive Loop Detector provides vehicle detection. Frequency and sensitivity can be set to eliminate problems with interference and false calls (cross-talk) from adjacent loops. In Pulse Mode, the detector provides an 150 millisecond pulse in response to a detection. In Presence Mode, the output from the detector is active as long as a vehicle is present on the loop. An LED indicates when a vehicle is on the loop or if Delay or Extension is active. Photo shows a rack-mounted detector. Detectors also come as a stand-alone unit.

Manufacturer

Naztec, Inc., Sugarland, TX
http://www.naztec.com


Traffic Signal Controller Manufacturers

The manufacturers listed below offer traffic signal controller and related products. Other manufacturers may exist.

Eagle Traffic Control Systems
8004 Cameron Road
Austin, TX 78754-3899
Telephone: (512) 837-8310
Fax: (512) 837-0196
E-mail: info@eagletcs.com
Web site: http://www.eagletcs.com

Econolite Control Products, Inc.
3360 E. La Palma
Anahim, CA 92806-2856
Telephone: (714) 630-3700
Fax: (714) 630-6349
E-mail: sales@econolite.com
Web site: http://www.econolite.com

Peek Traffic, Inc.
1500 N. Washington Blvd.
Sarasota, FL 34236
Telephone: (941) 366-8770
Fax: (941) 365-0837
E-mail: usinfo@peekglobal.com
Web site: http://www.peekglobal.com

Naztec, Inc
820 Park Two Dr.
Sugar Land, TX 77478, USA.
Telephone: (281) 240-7233
Fax: (281) 240-7238
E-mail: naztec@naztec.com
Web site: http://www.naztec.com

McCain Traffic Supply
2575 Pioneer Avenue
Vista, CA 92083
Telephone: (760) 727-8100
Fax: (760) 727-8264
E-mail: mccain@mccaintraffic.com
Web site: http://www.mccaintraffic.com

U.S. Traffic Corporation
9603 John Street
Santa Fe Springs, CA 90670
Telephone: (562) 923-9600
Fax: (562) 923-7555
E-mail: info@ustraffic.net
Web site: http://www.ustraffic.net


APPENDIX B - REFERENCES

  1. Manual on Uniform Traffic Control Devices (MUTCD). Millenium Edition. Federal Highway Administration (FHWA), Washington, D.C., 2000.
  2. Bentzen, B.L. & Tabor, L.S.(1998). Accessible Pedestrian Signals.U.S. Access Board, Washington, D.C.,1998.
  3. Building a True Community. Final Report. Public Rights-of-Way Access Advisory Committee (PROWAAC), U.S. Access Board, Washington, D.C.,January 2001.
  4. History Web Site. http://www.sonic.net/~lindam/historyday/history.html, Accessed October 1, 2002.
  5. Pline, James L. (Ed.). Traffic Control Devices Handbook. Institute of Transportation Engineers, Washington, D.C., 2001.
  6. Traffic Control System Operations: Installation, Management, and Maintenance. Institute of Transportation Engineers (ITE), Washington,D.C., 2000.
  7. Barlow, J.M., Bentzen, B.L., & Tabor, L.S. Accessible Pedestrian Signals: Synthesis and Guide to Best Practice. Draft Report. National Cooperative Highway Research Program, Project 3-62, January 2003.
  8. Bentzen, B., Barlow, J., Franck, L. Determining Recommended Language for Speech Messages used by Accessible Pedestrian Signals: Final Report.Accessible Design for the Blind, Berlin, MA, January, 2002.